Safe Pathway Illumination
Emergency corridor lighting ensures safe evacuation by providing adequate illumination along escape routes during power failures. Our high-temperature battery packs are designed for bulkhead lights, downlights, and linear fixtures installed in corridors, stairwells, and passageways where ambient temperatures can be challenging.
US Market Standards
UL 924, NFPA 101 & IBC Compliance
US emergency corridor lighting must comply with UL 924, NFPA 101 Life Safety Code, and International Building Code (IBC). These standards ensure adequate illumination for safe egress during emergencies.
Battery backup must provide at least 90 minutes of illumination
Minimum illumination required along the path of egress
Ratio between maximum and minimum illumination levels
10 footcandles required at stair treads during emergency
US Technical Specifications
| Standards | UL 924, NFPA 101, IBC |
| Battery Runtime | ≥90 minutes |
| Floor Illumination | ≥1 footcandle (10.76 lux) |
| Stairway Illumination | ≥10 footcandles |
| Uniformity Ratio | ≤40:1 (max:min) |
| Fixture Spacing | Per photometric design |
| Monthly Test | 30 seconds functional |
EU Technical Specifications
| Standards | EN 1838, EN 60598-2-22 |
| Battery Runtime | ≥1 hour (3 hours typical) |
| Escape Route (center) | ≥1 lux |
| Escape Route (band) | ≥50% of center line |
| Uniformity Ratio | ≤40:1 (max:min) |
| Anti-Panic Area | ≥0.5 lux |
| Glare Limit (UGR) | ≤25 (below eye level) |
European Market Standards
EN 1838 & EN 60598-2-22 Compliance
European emergency escape route lighting is governed by EN 1838 (Lighting applications - Emergency lighting) and EN 60598-2-22 (Luminaires for emergency lighting). These standards define illumination levels, uniformity, and duration requirements.
Center line of escape route up to 2m wide must have ≥1 lux
Most European countries require 3-hour emergency duration
Open areas >60m² require 0.5 lux minimum horizontal illumination
Emergency lighting must reach 50% output within 5 seconds
Corridor Lighting Fixture Types
Our batteries power various emergency corridor lighting fixtures
Emergency Downlights
Recessed ceiling-mounted fixtures for modern corridors
Bulkhead Lights
Robust wall-mounted fixtures for stairwells and corridors
Linear Fixtures
Continuous lighting for long corridors and passageways
Twin Spot Heads
Adjustable emergency spotlights for targeted illumination
Recommended Battery Solutions
High-temperature batteries designed for corridor emergency lighting applications
NiCd SC2000 Pack
Ideal for enclosed bulkhead and downlight fixtures
- +70°C maximum operating temp
- 3-hour runtime at +55°C
- 4-year design life